Investigation Report
Heater Treater Overheating on Offshore Platform
09-09-2019 23:00 G05431 VR 252 Fire, Incident >$25K
- BSEE
- Investigation Report
- Unknown
- CorrosionFunctional safetyMechanical failureProcess safety
- Inspection and maintenance
- Pressure vesselValve
- Alarm managementFunctional testingPreventive maintenanceStop-work authority
- Upstream oil and gas
- Offshore installation
Summary
BSEE investigates heater treater overheating at Castex’s Vermilion 252-A platform on 9–10 September 2019. The report examines burner adjustment, restricted exhaust flow, ineffective temperature shutdowns, inadequate thermowell installation and delayed shut-in. It records equipment damage, inspection deficiencies and subsequent liquid-level corrections, while retaining uncertainty over several contributing mechanisms.