Investigation Report

Heater Backfire During Platform Restart After Emergency Shutdown Testing

BSEEBureau of Safety and Environmental Enforcement

03-16-2015 16:30 G02719 HI A 582 Explosion / Structural Damage / Equipment Failure

Read at BSEEOpens the document on bsee.gov

Summary

This investigation examines an Ambitrol heater backfire during platform restart following emergency shutdown testing. Inadequate purging, unreliable air/fuel ratio valve operation and excess fuel admitted by the programmable logic controller allowed an explosive mixture to accumulate. The heater cover was dislodged; no personnel injury, environmental incident or fire resulted.

Topics

About This Record
Original title
03-16-2015 16:30 G02719 HI A 582 Explosion / Structural Damage / Equipment Failure
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Explosion, Functional Safety, Mechanical Failure
Activity
Inspection and Maintenance
Equipment
Valve
Control
Functional Testing, Stop-Work Authority
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-8b7a647513 · added 2 October 2026

Report a problem with this record