Investigation Report
Fire on Unmanned Platform Following Release onto Reboiler
06-30-2005 12:05 G25601 HI/A287 Fire
- BSEE
- Investigation Report
- Unknown
- FireHydrocarbon releaseMechanical failure
- HoseProcess pipework and pipelinesPumpsValve
- Fire protectionEnergy and process isolation
- Upstream oil and gas
- Offshore installation
Summary
Investigation of a fire on the unmanned HI A-287 platform. Suspected vibration-related tubing fitting failure released condensate, glycol and gas onto a reboiler. The report describes renewed burning, valve failures and damaged extinguisher hoses, and recommends an alert advocating hard piping and additional bracing.
Classifications: Fire; fire safety.
Classifications: Hydrocarbon release; hydrocarbon leak; oil and gas release.
Classifications: Mechanical failure; equipment failure.
Classifications: Hose; flexible hose.
Classifications: Process pipework and pipelines; process piping.
Classifications: Pumps.
Classifications: Valve; valves.
Classifications: Fire protection; fire suppression; fire detection.
Classifications: Energy and process isolation; isolation; energy isolation.
Classifications: Upstream oil and gas; oil and gas extraction; upstream petroleum.