Investigation Report
Heater-Treater Fire Fed by Oil Through Pitted Fire Tube
Read at BSEEOpens the document on bsee.gov
Summary
Investigation of a heater-treater fire at Vermillion 369-A on 18 April 2014. Acid batch treatments caused or accelerated fire-tube pitting, allowing produced oil to feed the fire after burner gas isolation. The report identifies failure to inspect following earlier warnings and describes manual shutdown and successful extinguisher use.