Investigation Report

Heater-Treater Fire Fed by Oil Through Pitted Fire Tube

BSEEBureau of Safety and Environmental Enforcement

04-18-2014 19:00 G02274 VR 369 A Fire / Equipment Failure

Read at BSEEOpens the document on bsee.gov

Summary

Investigation of a heater-treater fire at Vermillion 369-A on 18 April 2014. Acid batch treatments caused or accelerated fire-tube pitting, allowing produced oil to feed the fire after burner gas isolation. The report identifies failure to inspect following earlier warnings and describes manual shutdown and successful extinguisher use.

Topics

About This Record
Original title
04-18-2014 19:00 G02274 VR 369 A Fire / Equipment Failure
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Corrosion, Fire, Hydrocarbon Release, Mechanical Failure, Structural and Asset Integrity
Activity
Inspection and Maintenance
Equipment
Pressure Vessel, Pumps, Valve
Control
Fire Protection, Energy and Process Isolation
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link
Checked , working
Record
bsee-39ee1c8487 · added 2 October 2026