An investigation examines a production-platform explosion after compressor starting failures. Low-pressure gas migrated from a water skimmer through deck penetrations into the motor control centre room, where a relay ignited trapped gas. Recommendations address sealing penetrations, modifying blowdown pipework or installing a flow safety valve, and checking buildings for migration paths.

Topics

About This Record
Original title
02-23-2004 14:00 G02688 HI/467 Explosion
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Electrical Safety, Explosion, Hydrocarbon Release
Equipment
Process Pipework and Pipelines, Switchgear, Valve
Control
Atmospheric Gas Testing, Ventilation
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link