Investigation Report

Hydrogen Sulphide Released from Ruptured Glycol Vessel Piping

BSEEBureau of Safety and Environmental Enforcement

01-06-2005 00:26 P00450 SM/6524 Gas Release

Read at BSEEOpens the document on bsee.gov

Summary

This investigation records a hydrogen sulphide gas release from ruptured three-quarter-inch piping attached to a glycol vessel on Platform Hidalgo’s production deck. The vessel operated at approximately 1285 psi with approximately 19,500 ppm H2S. Gas detection initiated an alarm and emergency shutdown; similar piping was undergoing ultrasonic non-destructive inspection.

Topics

About This Record
Original title
01-06-2005 00:26 P00450 SM/6524 Gas Release
Publisher
Bureau of Safety and Environmental Enforcement
Type
Investigation Report
Date
Unknown
Topic
Hydrogen Sulphide, Loss of Containment, Mechanical Failure, Pressure Systems
Activity
Inspection and Maintenance
Equipment
Gas Detector, Process Pipework and Pipelines
Control
Non-Destructive Testing
Sector
Upstream Oil and Gas
Setting
Offshore Installation
Link