Safety Flash
Unexpected Release of Water During Annual Maintenance of CO2 Fixed Firefighting System
Read at IMCAOpens the publisher’s page on imca-int.com
Summary
During annual maintenance of a vessel’s fixed CO2 firefighting system, air blown through lines at 7 bar unexpectedly discharged water onto electrical switchboards and transformers. The water source remained unidentified, with condensation suspected. Work stopped, nozzle covers were introduced and maintenance instructions revised; compressed-air systems should be blown through before connection.