Safety Alert
BSEE Identifies Maintenance and Certification Issues of Rental Generators
Read at BSEEOpens the publisher’s page on bsee.gov
Summary
BSEE reviews rental generator incidents during start-up and commissioning on the US Outer Continental Shelf in 2021. Failures involved fires, arc flashes and work stoppages. The alert discusses degraded windings, moisture ingress and corrosion, and recommends operators consider certification checks, commissioning assurance, insulation resistance testing and personnel competence measures.