Safety Alert
Safety Alert 15 - Electrical Cable Testing
Read at BSEEOpens the publisher’s page on bsee.gov
Summary
A Pacific OCS platform fire followed insulation testing of a submersible pump power cable when grounding produced a spark that ignited escaping well-annulus gas. The alert recommends avoiding rig-floor testing, using purged rooms where feasible, requiring permits and continuous flammable-gas monitoring in non-purged environments, and reducing sparking through suitable instruments and capacitance discharge.