Safety Alert
Safety Alert 142 - Pollution Because of Failure of Level Safety High Sensor and Level Controller
Read at BSEEOpens the publisher’s page on bsee.gov
Summary
An oil tank’s level controller and high-level safety sensor failed, allowing oil into a low-pressure flare scrubber. Two barrels were blown overboard when the compressor shut down and routinely vented gas. Paraffin blocked the float cage, and the controller float was set too high. Planned measures include float repositioning and periodic solvent injection.