Investigation Report
Eye Injury from Gas and Debris During Orifice Plate Check
Read at BSEEOpens the document on bsee.gov
Summary
An investigation examines an operator’s eye injury while checking an orifice plate on a production platform. Loosening clamp bolts released natural gas and debris at approximately 915 PSIG. Findings identify an unclosed equaliser valve and a blocked blowdown valve that gave a false impression of depressurisation. Medical treatment included irrigation and surgery.