Investigation Report
Gas Release and Water Hammer Following Compressor Shutdown
Read at BSEEOpens the document on bsee.gov
Summary
Investigation of a gas release at Mad Dog following compressor shutdown. Flare backpressure caused tandem rupture discs to fail, allowing gas into seawater cooling pipework and causing water hammer and damage. The report examines earlier failures and recommends check valves, revised pressure protection, flare modifications and delayed seawater pump shutdown.