Investigation Report
Electrical Arcing and Fire in Jack-Up Rig SCR Room
Read at BSEEOpens the document on bsee.gov
Summary
An investigation describes electrical arcing and fire in the Hercules 253 jack-up rig’s SCR room. Accumulated soot and contaminants provided a conductive path between generator busbars and ground. The report identifies inadequate inspection and maintenance as contributing factors and recommends regular SCR panel inspections with maintenance programmes based on their findings.