Investigation Report

Hot Oil Heater Explosion During Restart

BSEEBureau of Safety and Environmental Enforcement

01-14-2006 03:00 G01316 MP/299 Fire - Explosion

Read at BSEEOpens the document on bsee.gov

Summary

Investigation of a hot oil heater explosion during restart identifies restricted pilot fuel flow from condensate, shutdown valves failing to close fully and departure from start-up procedures. High winds may also have inhibited ignition. Recurrence measures included redundant shutdown valves, fuel filtration, quarterly maintenance and revised purge timing and damper sequencing.